07-08-2017
Output Power Capacity
16 kW / 20 kVA
Max Configurable Power
16 kW / 20 kVA
Nominal Output Voltage
230V
Output Voltage Note
Configurable for 400 or 415V 3 Phase nominal output voltage
Output Voltage Distortion
Less than 5%
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Other Output Voltages
220, 240
Topology
Double Conversion Online
Output Connections
(1) Hard Wire 3-wire (H N + G) |
|
(1) Hard Wire 5-wire (3PH + N + G) |
|
(8) IEC 320 C19 |
|
(2) IEC Jumpers |
|
Overload Operation
60 seconds @ 125% and 30 seconds @ 150%
Bypass
Built-in Static Bypass, Internal Bypass (Automatic and Manual), Optional External Bypass
-
07-08-2017
Output Power Capacity
2100 Watts / 3000 VA
Max Configurable Power
2100 Watts / 3000 VA
Nominal Output Voltage
230V
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
Efficiency at Full Load
92%
Output Voltage Distortion
Less than 3%
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Output Connections
(8) IEC 320 C13 |
|
(2) IEC 320 C19 |
|
(3) IEC Jumpers |
|
Bypass
Internal Bypass (Automatic and Manual)
-
08-08-2017
Includes: CD with software, Rack Mounting brackets, Smart UPS signalling RS-232 cable, User Manual
Trang: 1